Designed for power and control, telemetering, relay control, traffic control,
switching, lighting and signal transmission. May be used in Class 1, Div. 2
Hazardous Locations per NEC Art. 501. These cables also conform to Art. 318
"Cable Trays" and Art 340 "Power and Control Tray Cable."
|
Specifications:
- CONDUCTORS: Class B stranded bare copper per UL 83 and 62
- INSULATION: Polyvinyl Chloride (PVC) per UL 62 for Type TFFN (18-16 AWG)
or
UL 83 for Type THWN or THHN wire, nominal thickness is 15 mils for sizes
18-12 AWG and 20 mils for 10 AWG
- INSULATION JACKET: Each insulated conductor is jacketed with nylon
meeting
UL 62 for Type TFFN or UL 83 for Type THWN or THHN wire, minimum
thickness is 4 mils
- COLOR CODE: ICEA Method 1, Table E-2 (formerly K-2)
- ASSEMBLY: Conductors are cabled with fillers where necessary to make
round,
two conductor cables are flat
- OVERALL JACKET: Sunlight-resistant Polyvinyl Chloride (PVC) per UL 1277
- STANDARDS: Meets UL requirements for Type TC cables having THWN or
THHN
(TFFN) conductors, cables are listed for direct burial and meet the IEEE
1202, UL 1277 and ICEA 70,000 BTU Flame Tests
- AMPACITY: Based on not more than three conductors in raceway or cable
or
earth with an ambient temperature of 30?C per NEC Table 310.16, the values
have been derated where applicable
- TEMPERATURE: 90?C
- VOLTAGE: 600 V
|