The Panel is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses
conventional input devices. The panel accepts water flow devices, two-wire
smoke detectors, four-wire smoke detectors, pull stations and other
normally-open contact devices. Outputs include four Notification Appliance
Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and
supervisory) and an EIA-485 port to interface with remote annunciators and
optional remote relay modules. The FACP is field programmable via the panel
keypad. It also supervises all wiring, AC voltage and battery level.
This series of panels are basically the same in application and operation, their
differences are shown in Table 1-1. The Panel will be described as the example in
the following sections.
Table 1-1
FACP Number of
Detection Zones
Number of
Sounder Outputs
Output Delay
Settings
ZONE-4 4 1 N/A
ZONE-8 8 2 N/A
ZONE-16 16 4 N/A
1.1 Product Features
l 4,8,16 Class B Initiating Device Circuits (IDCs)
? All zones accept conventional detectors and any normally open
contact device
l Four Class B Notification Appliance Circuits (NACs)
l One Form-A Alarm Relay
l One Form-A Trouble Relay
l One Form-A Supervisory Relay
l 3.0 amps of system power
l Max 20 conventional detectors in one zone.
l Auto/Manual mode setting enable walk test.
l Each Zone can be disabled,
l Sound output can be disabled.
l Manual active sound output enabled.

AC Power
90 to 270 VAC, 50 /60 Hz, 2.3 amps
Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation
Battery (lead acid only)
Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp
Maximum Charger Capacity: 18 Amp Hour batter
Sound Output Device Circuits
General Alarm Zones 1 through 16
Operation: All zones Class B
Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)
Alarm Current: 15 mA threshold
Short Circuit Current: 42 mA maximum
Maximum Loop Resistance: 100 ohms
End-of-Line Resistor: 4.7K, ? watt
Detector Loop Current is sufficient to ensure operation of two alarmed detectors
per zone
Standby Current: 7.26 mA
Three Relays Output
Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC
(resistive)
Nonresettable 24 VDC Power
Maximum ripple voltage: 10 mVRMS Operating Voltage nominal 24 volts
Total DC current available from this output is up to 500 mA
Recommended maximum Standby current is 150 mA