厂商 :青岛青缆科技有限责任公司
山东 青岛市- 主营产品:
- UL认证美标电缆
- UL83标准THHN
- UL1569铠装电缆
MC Cable
Type and designation
Type |
designation |
MC |
Lightweight Aluminum Interlocked Armored Cable |
Description of the
pure
MC Cable is suitable for use as follows:
? Branch, feeder and service power distribution in commercial, industrial,
institutional, and multi-residential buildings.
? Power, lighting, cool, and signal circuits.
? Fished or embedded in plaster.
? Concealed or exed installations.
? Environmental air-handling spaces per NEC 300.22 (C).
? Places of Assembly per NEC 518.4 and theaters per NEC 520.5.
? As aerial cable on a messenger.
? Installation in cable tray and approved raceways.
? Under raised floors for information technology equipment conductors and
cables per NEC 645.5(D) & 645.5(D) (2).
? Class I Div. 2, Class II Div 2, & Class III Div. 1 Hazardous Locations.
Standard
UL 83, UL 1063, UL 1569
Features
1, Reduces installation costs up to 50% over pipe and wire.
2, Lightweight aluminum armor--as much as 45% lighter than steel MC Cable.
3,UL Classified 1, 2, and 3 hour Through Penetration Firestop Systems:
W-J-3037, W-L-3110, W-L-3113, W-L-3117,W-L-3120, W-L-3121, W-L-3160, C-AJ-3115,
C-AJ-3140, C-AJ-3142, C-AJ-3145, C-AJ-3173, C-AJ-3202, C-AJ-4065,C-AJ-4066,
F-C-3038.
4, Cable reverse wound on reel for ease of pulling and installation. When
pulling from coils, pull from inside to ensure ease of installation.
Specification and Construction
MC Cable is constructed with soft-drawn copper, Type THHN/THWN conductors rated90°Cdry/75°Cwet, ailable in sizes 14 AWG through 750 kcmil, and a green insulated grounding conductor (sizes 1/0 AWG and larger furnished with bare grounding conductor). The conductors are cabled together and a binder tape bearing the print legend is wrapped around the assembly. Aluminum interlocking armor is applied over the assembly. Refer to color chart for conductor color sequence.
Conductor Size (AWG) |
Solid or Stranded |
Grounding Conductor Size (AWG) and Stranding |
Overall Diameter (inches) |
Approximate Weight |
Ampacity |
Standard Package |
|||
lbs./1000' |
kg./km. |
75°C |
90°C |
Coil (feet) |
Reel (feet) |
||||
14/4 |
Solid |
14 sol |
0.496 |
135 |
201 |
15 |
15 |
250 |
1000 |
12/2 |
19 |
12-19 |
0.508 |
119 |
178 |
20 |
20 |
250 |
1000 |
12/2 |
Solid |
12 sol |
0.480 |
115 |
171 |
20 |
20 |
250 |
1000 |
12/3 |
19 |
12-19 |
0.543 |
147 |
220 |
20 |
20 |
250 |
1000 |
12/3 |
Solid |
12 sol |
0.512 |
141 |
211 |
20 |
20 |
250 |
1000 |
12/4 |
19 |
12-19 |
0.579 |
176 |
262 |
20 |
20 |
250 |
750 |
12/4 |
Solid |
12 sol |
0.547 |
169 |
252 |
20 |
20 |
250 |
750 |
10/2 |
19 |
10-19 |
0.579 |
170 |
254 |
30 |
30 |
250 |
750 |
10/2 |
Solid |
10 sol |
0.550 |
165 |
246 |
30 |
30 |
250 |
750 |
10/3 |
19 |
10-19 |
0.622 |
213 |
318 |
30 |
30 |
250 |
500 |
10/3 |
Solid |
10 sol |
0.590 |
207 |
309 |
30 |
30 |
250 |
500 |
10/4 |
19 |
10-19 |
0.669 |
257 |
383 |
30 |
30 |
250 |
500 |
10/4 |
Solid |
10 sol |
0.634 |
250 |
373 |
30 |
30 |
250 |
500 |
8/2 |
19 |
10-19 |
0.660 |
230 |
343 |
50 |
55 |
200 |
500 |
8/3 |
19 |
10-19 |
0.724 |
301 |
449 |
50 |
55 |
200 |
500 |
8/4 |
19 |
10-19 |
0.790 |
372 |
555 |
50 |
55 |
125 |
500 |
6/2 |
19 |
8-19 |
0.753 |
329 |
491 |
65 |
75 |
125 |
500 |
6/3 |
19 |
8-19 |
0.825 |
433 |
646 |
65 |
75 |
125 |
500 |
6/4 |
19 |
8-19 |
0.900 |
537 |
801 |
65 |
75 |
100 |
500 |
4/3 |
19 |
8-19 |
0.956 |
624 |
931 |
85 |
95 |
100 |
500 |
4/4 |
19 |
8-19 |
1.056 |
789 |
1178 |
85 |
95 |
100 |
500 |
3/3 |
19 |
6-19 |
1.032 |
776 |
1158 |
100 |
110 |
100 |
500 |
3/4 |
19 |
6-19 |
1.139 |
980 |
1462 |
100 |
110 |
100 |
500 |
2/3 |
19 |
6-19 |
1.089 |
915 |
1365 |
115 |
130 |
100 |
500 |
2/4 |
19 |
6-19 |
1.207 |
1164 |
1737 |
115 |
130 |
100 |
500 |
Note: Ampacities are based on Table 310.16 of
the NEC, 2005 Edition.
Allowable ampacities shown are for general use as specified by the National
Electrical Code, 2005 Edition, Section 310.15.If the equipment is marked for
use at higher temperatures, the conductor ampacity shall be limited to the
following per NEC 110.14(C).75°C- When terminated to equipment for circuits rated over 100 amperes or marked
for conductors larger than size 1 AWG.90°C- For ampacity derating pures.
Per NEC 310.15(B)(2)(a), the ampacity of 4/C cables shall be reduced by a
factor of 0.80 when the neutral is considered a current-carrying conductor.
A vailable in sizes up to 750 kcmil.
COLOR CODING Standard Products
No. of Conductors |
Color Sequence |
2 |
Black, White |
3 |
Black, White, Red |
4 |
Black, White, Red, Blue |
Grounding Conductor |
Green or bare |
Other special colors are ailable subject to economic order quantity. |
- 供应美标UL1063标准MTW电缆THHN cable
- 供应美国UL83标准认证THHN10AWG尼龙护套电缆
- 供应菲律宾标准电缆THHN500mm250mm2
- 供应菲律宾THHN250mm2电缆 菲律宾THHN250mm500mm2电缆
- 供应美标UL83标准THHN500MCM美标UL认证电缆
- 供应UL83THHN500MCM通过UL认证THWN尼龙护套电缆
- 供应 UL认证UL1277标准TC-ER cable,tray cable,TC cable 托架用电缆TC
- 供应UL认证MC联锁铠装电缆符合UL1569标准MC-THHN,MC-XHHW-2
- 供应美国UL83标准THHN尼龙护套线THWN THWN-2生产厂家
- 供应加拿大CSA标准铠装电缆AC90 ACWU90 NMD90 cable