厂商 :广州广高高压电器有限公司
广东 广州- 主营产品:
- 油浸式电力变压器
- 干式变压器
- 单相柱上式配
广高牌 单相柱上式变压器 带盒子
Single Phase Pole-mounted Distribution Transformer CSP type with secondary cable box
Product application:
CSP type (Completely Self Protect) Single phase pole-mounted distribution transformers (with secondary cable box) are mainly used in the electricity transmission and distribution system, it can be used for lighting and power supply in all city, town and remote areas. One single phase pole mounted transformer can be used as a single phase transformer separately, and three single phase transformers can be also connected together, working as a three phase transformer. It saves cost, and it is safe, compact, be very easy for repairing and maintenance.
CSP type (Completely Self Protect) Single phase pole-mounted distribution transformers (with Secondary cable box) are especially equipped with one secondary circuit breaker, one primary fuse, one primary arrester and one secondary arrester, all these accessories can protect the transformer from over load, short circuit accident, thunder and lightning.
CSP type (Completely Self Protect) Single phase pole-mounted distribution transformers (with Secondary cable box) are especially equipped with one secondary cable box, it can be use to avoid electricity stealing.
Standards:
ANSI C57.12.00, ANSI C57.12.90, ANSI 057.1220,
ANSI C6211, ASTM D3487
Specification:
Frequency: 6oHZ. ONAN type
Primary voltage: 12.47 Grd. Y I72 kV, Secondary voltage: 120/24oV
Losses: see above table.
Taps: -7.5°/o,-5°/o,-2.5°/o, 0%, +25%
BIL of primary: 95KV, BIL of secondary: 3oKV
Power Frequency Withstand Voltage for Primary: 35KV;
Power Frequency Withstand Voltage for Secondary: 1oKV
Temperature rise: 65 Degree.
Construction and Accessories:
1.This type of transformer is constructed with silicon steel metal core. aluminum winding and mineral oil No PCB.are equipped with 1 HV busing on primary, 3 LV bushing on secondary, 2 lift lugs for lift complete transformer, 2 support lugs to fix on the pole, one pressure relief device and ground terminals.
2.This type of transformers are especially equipped with one secondary circuit breaker, one primary fuse, one primary arrester and one secondary arrester. all these accessories can protect the transformer from overload. short circuit accident, thunder and lightning.
3.especially equipped with one secondary cable box, it can be use to avoid electricity