厂商 :许昌华继电气有限公司
河南 许昌市- 主营产品:
- WXH-823
- WXH-822
- WXH-821
联系电话 :15537408000
商品详细描述
1.1. 二段电流保护(WXH-821)
WXH-821装置设二段电流保护,各段电流及时间定值可独立整定,通过分别设置保护压板控制这两段保护的投退。
表5-1 WXH-821定值范围
WXH-822定值范围见表5-2:
表5-2 WXH-822定值范围
1.1.
压板整定信息
WXH-821压板见表5-3:
表5-3 WXH-821软压板信息
WXH-821装置设二段电流保护,各段电流及时间定值可独立整定,通过分别设置保护压板控制这两段保护的投退。
表5-1 WXH-821定值范围
定值种类 |
定值项目(符号) |
整定范围及步长 |
1.电流Ⅰ段保护 |
电流Ⅰ段定值(Idz1) |
0.1In~20In,0.01A |
电流Ⅰ段时限(T1) |
0s~100s,0.01s |
|
2.电流II段保护 |
电流II段定值(Idz2) |
0.1In~20In,0.01A |
电流II段时限(T2) |
0s~100s,0.01s |
|
3.过流加速保护(前加速或后加速) |
过流加速定值(Ijs) |
0.1In~20In,0.01A |
过流加速时限(Tjs) |
0s~100s,0.01s |
|
前加速方式投退(QJS) |
0(后加速)/1(前加速) |
|
4.重合闸 |
重合闸时限(Tch) |
0.3s~10s,0.01s |
重合闸无压值(Udzch) |
4V~100V,0.01V |
|
重合闸同期角(Ach) |
5°~50°,0.01° |
|
重合闸方式(Mch) |
0(无检定)/1(检无压有压转检同期)/2(检同期)/3(检无压有压不合闸) |
|
抽取电压相别(TUx) |
0(Ua)/1(Ub)/2(Uc)/3(Uab)/4(Ubc)/5(Uca) |
|
遥控合闸方式(Myh) |
0(无检定)/1(检无压有压转检同期)/2(检同期)/3(检无压有压不合闸) |
|
5.低频减载 |
动作频率(f) |
45Hz~49.5Hz,0.01Hz |
动作时限(Tf) |
0s~100s,0.01s |
|
动作电压(Udzf) |
10V~90V,0.01V |
|
滑差定值(dfdt) |
0.3Hz/s~10Hz/s,0.01Hz/s |
|
滑差闭锁(DF) |
1(投入)/0(退出) |
|
6.零序电流保护 |
零序电流定值(I0dz) |
0.02A~12A,0.01A |
零序电流时限(T0) |
0s~100s,0.01s |
|
零序电流跳闸(I0TZ) |
1(投入)/0(退出) |
|
8.过负荷保护 |
过负荷定值(Igfh) |
0.1In~20In,0.01A |
过负荷时限(Tgfh) |
0s~600s,0.01s |
|
过负荷跳闸(GFHTZ) |
1(投入)/0(退出) |
|
9.低电压保护 |
低电压定值(Udz) |
4V~70V,0.01V |
低电压时限(Tdy) |
0s~100s,0.01s |
|
10.TV断线自检 |
TV断线投退(TV) |
1(投入)/0(退出) |
相关保护投退(BH) |
1(投入)/0(退出) |
表5-2 WXH-822定值范围
定值种类 |
定值项目(符号) |
整定范围及步长 |
1.电流Ⅰ段保护 |
电流Ⅰ段定值(Idz1) |
0.1In~20In,0.01A |
电流Ⅰ段时限(T1) |
0s~100s,0.01s |
|
电流Ⅰ段电压定值(Udz1) |
2.0V~100V,0.01V |
|
-30°灵敏角投退(ALM1) |
1(-30°)/0(-45°) |
|
电流Ⅰ段电压投退(UBS1) |
1(投入)/0(退出) |
|
电流Ⅰ段方向投退(DBS1) |
1(投入)/0(退出) |
|
3.电流II段保护 |
电流II段定值(Idz2) |
0.1In~20In,0.01A |
电流II段时限(T2) |
0s~100s,0.01s |
|
电流II段电压定值(Udz2) |
2.0V~100V,0.01V |
|
-30°灵敏角投退(ALM2) |
1(-30°)/0(-45°) |
|
电流II段电压投退(UBS2) |
1(投入)/0(退出) |
|
电流II段方向投退(DBS2) |
1(投入)/0(退出) |
|
4.电流Ⅲ段保护 |
电流Ⅲ段定值(Idz3) |
0.1In~20In,0.01A(投反时限时范围为0.1In~3In) |
延时方式(YSFS) |
0~3,1(0为定时限,1~3分别对应一般反时限,非常反时限,极端反时限) |
|
电流Ⅲ段时限(T3) |
0s~100s,0.01s(投反时限时范围为0.05s~1s) |
|
电流Ⅲ段电压定值(Udz3) |
2.0V~100V,0.01V |
|
-30°灵敏角投退(ALM3) |
1(-30°)/0(-45°) |
|
电流Ⅲ段电压投退(UBS3) |
1(投入)/0(退出) |
|
电流Ⅲ段方向投退(DBS3) |
1(投入)/0(退出) |
|
5.过流加速保护(前加速或后加速) |
过流加速定值(Ijs) |
0.1In~20In,0.01A |
过流加速时限(Tjs) |
0s~100s,0.01s |
|
前加速方式投退(QJS) |
0(后加速)/1(前加速) |
|
6.重合闸 |
重合闸时限(Tch) |
0.3s~10s,0.01s |
重合闸无压值(Udzch) |
4V~100V,0.01V |
|
重合闸同期角(Ach) |
5°~50°,0.01° |
|
重合闸方式(Mch) |
0(无检定)/1(检无压有压转检同期)/2(检同期)/3(检无压有压不合闸) |
|
抽取电压相别(TUx) |
0(Ua)/1(Ub)/2(Uc)/3(Uab)/4(Ubc)/5(Uca) |
|
遥控合闸方式(Myh) |
0(无检定)/1(检无压有压转检同期)/2(检同期)/3(检无压有压不合闸) |
|
7.低频减载保护 |
动作频率(f) |
45Hz~49.5Hz,0.01Hz |
动作时限(Tf) |
0s~100s,0.01s |
|
动作电压(Udzf) |
10V~90V,0.01V |
|
滑差定值(dfdt) |
0.3Hz/s~10Hz/s,0.01Hz/s |
|
滑差闭锁(DF) |
1(投入)/0(退出) |
|
8.零序电流保护 |
零序电流定值(I0dz) |
0.02A~12A,0.01A |
零序电流时限(T0) |
0s~100s,0.01s |
|
零序电流跳闸(I0TZ) |
1(投入)/0(退出) |
|
9.过负荷保护 |
过负荷定值(Igfh) |
0.1In~20In,0.01A |
过负荷时限(Tgfh) |
0s~600s,0.01s |
|
过负荷跳闸(GFHTZ) |
1(投入)/0(退出) |
|
10.低电压保护 |
低电压定值(Udz) |
4V~70V,0.01V |
低电压时限(Tdy) |
0s~100s,0.01s |
|
11.TV断线检测 |
TV断线投退(TV) |
1(投入)/0(退出) |
相关保护投退(XGBH) |
1(投入)/0(退出) |
WXH-821压板见表5-3:
表5-3 WXH-821软压板信息
压板名称 |
控制字 |
电流Ⅰ段压板 |
投入/退出 |
电流Ⅱ段压板 |
投入/退出 |
过流加速压板 |
投入/退出 |
重合闸压板 |
投入/退出 |
低频减载压板 |
投入/退出 |
零序电流压板 |
投入/退出 |
过负荷压板 |
投入/退出 |
低电压压板 |
投入/退出 |
- WXH-821许继微机线路保护装置:http://www.xchjdq.com/product/WXH821131284_pro.html